V-Bala-250kW/522kWh Liquid-cooled Energy Storage Cabinet

522 kWh integrated LFP cabinet with two 125 kW PCS units

Home/Products/C&I Storage/V-Bala-250kW/522kWh Liquid-cooled Energy Storage Cabinet
C&I Storage

V-Bala-250kW/522kWh Liquid-cooled Energy Storage Cabinet

The V-Bala-250kW/522kWh integrates a 522 kWh LFP battery, two 125 kW PCS units, BMS and thermal management. Liquid cooling, multi-level fire protection and modular components support reliable operation, maintenance and AC-side parallel expansion.

  • 522 kWh rated energy with two 125 kW PCS units
  • 400 V AC output with parallel capacity expansion
  • System AC efficiency ≥90% and 100% depth of discharge
  • Liquid-cooled battery: cell temperature ≤35 °C and temperature difference ≤3 °C
  • Gas detection, emergency exhaust, aerosol and water-based fire protection
  • IP55 protection and C5 corrosion resistance
  • Modular battery pack and PCS design

Specifications

Product Model VN-CE0522L-L3P
Product Name V-Bala-250kW/522kWh
Chemistry LFP
Configuration 2 × 1P260S
Nameplate Energy 522 kWh
Cell Capacity 314 Ah
C-Rate ≤0.5P
Rated Voltage 832 V
Rated Power 250 kW (2 × 125 kW)
Max Power 300 kW (2 × 150 kW)
Output Voltage 400 V (-15% to +10%)
Power Factor >0.99 (adjustable -1 to 1)
Frequency 50/60 Hz
Cooling Method Liquid cooling (battery) / air cooling (PCS)
FSS Configuration Gas detection, emergency exhaust, aerosol & water fire suppression
Operating Temperature -35 to 55 °C (derating above 45 °C)
Operating Humidity 0–95% (non-condensing)
Charge-discharge Switching Time <100 ms
Noise Level ≤80 dB
Anti-corrosion Level C5
Altitude ≤2000 m
Ingress Protection Rating IP55
Weight 4500 kg
Dimensions (L × W × H) 1850 × 1350 × 2350 mm
Certifications CQC, LVRT/HVRT, IEC 62477, IEC 61000, EN 50549-1, EN 50549-2, UN38.3

Specifications and models are subject to change without prior notice.